Voltage Drop Calculator

SWA cable size calculator for sheds and garden rooms

Voltage drop on a steel wire armoured cable to a shed, garden room, garage or EV charger, in mm² and metres, against the BS 7671 figures: 3% for lighting and 5% for other uses.

Result

Copper, 75 °C basis
230 V224.28 VSOURCELOAD6 mm² copper25 m
Wire size6 mm²
Voltage drop5.72 V
Percent drop2.49 %
At the load224.28 V

Within 3% target

6 mm². Drop 5.72 volts, 2.49 percent. Within 3% target.

How this is worked out

V = 2 × ρ × I × L ÷ A

2 × 0.02145 × 32 A × 25 m ÷ 6 mm² = 5.72 V

5.72 V ÷ 230 V × 100 = 2.49 %. At the load: 230 V − 5.72 V = 224.28 V.

  • L is the one-way length; the 2 counts the return conductor.
  • ρ is 0.02145 for copper and 0.03524 for aluminum, in ohm·mm² per metre: the same 75 °C basis as K = 12.9 and 21.2 in US units.
  • Not checked here: temperature derating, conduit fill, power factor and code compliance.

Method and sources

Inputs

Wire sizes
Length in
Circuit type
Supply voltage

Source to load. The return wire is counted for you.

Conductor material
Allowed drop

Guidance, not a legal limit. See the questions below.

What to find

After derating for temperature and conduit fill. The tool does not hold ampacity tables.

What BS 7671 asks for

Worked example: a garden office 25 m away

A 32 A supply to a garden office, 25 m of copper SWA from the house, at 230 V:

SWA sizeDropLeft for lightingLeft for other uses
4 mm²3.73%none1.27%
6 mm²2.49%0.51%2.51%
10 mm²1.49%1.51%3.51%

6 mm² is the smallest size within 3% (5.72 V), which is where the calculator above starts. But that leaves the lights in the office almost nothing, so if the office has lighting circuits, a larger SWA leaves room for them.

Splitting the budget

Decide how much of the 3% and 5% the SWA may use, then enter that share as a custom target in the calculator. Whatever the SWA uses, the circuits in the outbuilding get the rest:

SWA dropLeft for lightingLeft for other uses
1%2%4%
1.5%1.5%3.5%
2%1%3%
2.5%0.5%2.5%
3%0%2%

The cable from the meter to the consumer unit in the house counts too, but on a short run its share is small.

The mV/A/m method and this calculator

UK electricians work out drop with the mV/A/m figures in BS 7671 Appendix 4: drop in volts = mV/A/m × design current × route length in metres ÷ 1000. For multicore armoured copper cable the figures are in Tables 4D4B (cable rated at 70 °C) and 4E4B (rated at 90 °C).

This calculator works from conductor resistance instead (the formula and constants are on the method page), so you don’t need the tables. Two differences:

SWA cable types

Voltage drop is one of several checks

Common sizes

6 mm² and 10 mm² are the sizes most often used for sheds and garden offices, with 10 mm² for longer runs or heavier loads. That is common practice, not a recommendation: put your own current and length into the calculator.

Frequently asked questions

What voltage drop does BS 7671 allow?

A design is deemed to comply when the drop from the origin of the installation to the equipment is within 3% for lighting and 5% for other uses, on a normal public supply. On 230 V that is 6.9 V and 11.5 V. These are deemed-to-satisfy figures from Appendix 4, not hard legal limits: what the regulations require is that each piece of equipment gets a voltage it can work with.

What size SWA do I need for a shed or garden office?

It depends on the current and the length. 6 mm² and 10 mm² are the sizes most often used for sheds and garden offices, with 10 mm² for longer runs or heavier loads, but that is common practice, not a rule. Enter your own run above, then check the cable’s current rating and the earth fault loop impedance with an electrician.

Do I enter 230 V or 240 V?

230 V, the UK nominal voltage. The supply may vary from about 216 V to 253 V (230 V +10% / −6%), and the drop in volts is the same whatever the supply voltage is.

What current do I enter?

The design current: the most the outbuilding will draw at once. If you do not know it, the rating of the breaker that feeds the SWA is a safe upper figure.

Does this calculator check the cable’s current rating?

No. It holds no BS 7671 current-rating tables. Enter the rating for your cable and installation method, from the tables or the cable maker’s datasheet, in the optional ampacity field, and the calculator checks your current against it.

Do I need to tell building control?

In England a new circuit to an outbuilding is notifiable under Part P: use a registered electrician or tell building control before you start. In Wales new circuits and new outdoor wiring are notifiable. Scotland has no Part P; a new circuit in a typical house needs no building warrant but must still meet the building regulations. As of November 2026; check with your council.