Wire gauge chart and converter
Convert AWG (also sold as B&S) to mm², kcmil and diameter, and back. Every value is worked out from the AWG formula, not copied from a table.
Convert from
1/0 is also written 0, and 2/0 as 00.
Conversion
Copper resistance at 75 °C| 6 AWG | 13.3 mm² |
| B&S gauge | 6 B&S |
| Metric size, same or larger | 16 mm² |
| Metric size, next smaller | 10 mm² |
| Area | 13.3 mm² · 26,251 cmil |
| Diameter, solid | 4.12 mm · 0.162 in |
| Resistance | 1.61 Ω/km · 0.491 Ω/1000 ft |
Choose the size with at least the same area, then check its ampacity in your code book. A size chart does not say how much current a wire may carry.
6 AWG is 13.3 mm². Metric size, same or larger: 16 mm².
AWG and B&S wire gauge chart
From 4/0, the largest gauge, to 40 AWG. B&S sizes are the same: 6 B&S is 6 AWG. Values are rounded to 3 significant figures.
| AWG / B&S | Diameter (in) | Diameter (mm) | Area (cmil) | Area (mm²) | Ω per 1000 ft | Ω per km |
|---|---|---|---|---|---|---|
| 4/0 | 0.460 | 11.7 | 211,600 | 107 | 0.0610 | 0.200 |
| 3/0 | 0.410 | 10.4 | 167,806 | 85.0 | 0.0769 | 0.252 |
| 2/0 | 0.365 | 9.27 | 133,077 | 67.4 | 0.0969 | 0.318 |
| 1/0 | 0.325 | 8.25 | 105,535 | 53.5 | 0.122 | 0.401 |
| 1 | 0.289 | 7.35 | 83,693 | 42.4 | 0.154 | 0.506 |
| 2 | 0.258 | 6.54 | 66,371 | 33.6 | 0.194 | 0.638 |
| 3 | 0.229 | 5.83 | 52,635 | 26.7 | 0.245 | 0.804 |
| 4 | 0.204 | 5.19 | 41,741 | 21.2 | 0.309 | 1.01 |
| 5 | 0.182 | 4.62 | 33,102 | 16.8 | 0.390 | 1.28 |
| 6 | 0.162 | 4.12 | 26,251 | 13.3 | 0.491 | 1.61 |
| 7 | 0.144 | 3.66 | 20,818 | 10.5 | 0.620 | 2.03 |
| 8 | 0.128 | 3.26 | 16,510 | 8.37 | 0.781 | 2.56 |
| 9 | 0.114 | 2.91 | 13,093 | 6.63 | 0.985 | 3.23 |
| 10 | 0.102 | 2.59 | 10,383 | 5.26 | 1.24 | 4.08 |
| 11 | 0.0907 | 2.30 | 8,234 | 4.17 | 1.57 | 5.14 |
| 12 | 0.0808 | 2.05 | 6,530 | 3.31 | 1.98 | 6.48 |
| 13 | 0.0720 | 1.83 | 5,178 | 2.62 | 2.49 | 8.17 |
| 14 | 0.0641 | 1.63 | 4,107 | 2.08 | 3.14 | 10.3 |
| 15 | 0.0571 | 1.45 | 3,257 | 1.65 | 3.96 | 13.0 |
| 16 | 0.0508 | 1.29 | 2,583 | 1.31 | 4.99 | 16.4 |
| 17 | 0.0453 | 1.15 | 2,048 | 1.04 | 6.30 | 20.7 |
| 18 | 0.0403 | 1.02 | 1,624 | 0.823 | 7.94 | 26.1 |
| 19 | 0.0359 | 0.912 | 1,288 | 0.653 | 10.0 | 32.9 |
| 20 | 0.0320 | 0.812 | 1,022 | 0.518 | 12.6 | 41.4 |
| 21 | 0.0285 | 0.723 | 810 | 0.410 | 15.9 | 52.2 |
| 22 | 0.0253 | 0.644 | 642 | 0.326 | 20.1 | 65.9 |
| 23 | 0.0226 | 0.573 | 509 | 0.258 | 25.3 | 83.1 |
| 24 | 0.0201 | 0.511 | 404 | 0.205 | 31.9 | 105 |
| 25 | 0.0179 | 0.455 | 320 | 0.162 | 40.3 | 132 |
| 26 | 0.0159 | 0.405 | 254 | 0.129 | 50.8 | 167 |
| 27 | 0.0142 | 0.361 | 202 | 0.102 | 64.0 | 210 |
| 28 | 0.0126 | 0.321 | 160 | 0.0810 | 80.7 | 265 |
| 29 | 0.0113 | 0.286 | 127 | 0.0642 | 102 | 334 |
| 30 | 0.0100 | 0.255 | 101 | 0.0509 | 128 | 421 |
| 31 | 0.00893 | 0.227 | 79.7 | 0.0404 | 162 | 531 |
| 32 | 0.00795 | 0.202 | 63.2 | 0.0320 | 204 | 670 |
| 33 | 0.00708 | 0.180 | 50.1 | 0.0254 | 257 | 844 |
| 34 | 0.00630 | 0.160 | 39.8 | 0.0201 | 325 | 1,065 |
| 35 | 0.00561 | 0.143 | 31.5 | 0.0160 | 409 | 1,343 |
| 36 | 0.00500 | 0.127 | 25.0 | 0.0127 | 516 | 1,693 |
| 37 | 0.00445 | 0.113 | 19.8 | 0.0100 | 651 | 2,135 |
| 38 | 0.00397 | 0.101 | 15.7 | 0.00797 | 820 | 2,692 |
| 39 | 0.00353 | 0.0897 | 12.5 | 0.00632 | 1,035 | 3,394 |
| 40 | 0.00314 | 0.0799 | 9.89 | 0.00501 | 1,305 | 4,280 |
mm² to AWG chart
Metric cable is sold in the IEC 60228 sizes. The equivalent gauge is the exact match. To swap a metric cable for a US one, choose the size with at least the same area.
| Metric size | Area (cmil) | Equivalent gauge | US size, same or larger | US size, next smaller |
|---|---|---|---|---|
| 0.5 mm² | 987 | 20.1 AWG | 20 AWG | 22 AWG |
| 0.75 mm² | 1,480 | 18.4 AWG | 18 AWG | 20 AWG |
| 1 mm² | 1,974 | 17.2 AWG | 16 AWG | 18 AWG |
| 1.5 mm² | 2,960 | 15.4 AWG | 14 AWG | 16 AWG |
| 2.5 mm² | 4,934 | 13.2 AWG | 12 AWG | 14 AWG |
| 4 mm² | 7,894 | 11.2 AWG | 10 AWG | 12 AWG |
| 6 mm² | 11,841 | 9.4 AWG | 8 AWG | 10 AWG |
| 10 mm² | 19,735 | 7.2 AWG | 6 AWG | 8 AWG |
| 16 mm² | 31,576 | 5.2 AWG | 4 AWG | 6 AWG |
| 25 mm² | 49,338 | 3.3 AWG | 3 AWG | 4 AWG |
| 35 mm² | 69,073 | 1.8 AWG | 1 AWG | 2 AWG |
| 50 mm² | 98,676 | between 1 and 1/0 AWG | 1/0 AWG | 1 AWG |
| 70 mm² | 138,147 | between 2/0 and 3/0 AWG | 3/0 AWG | 2/0 AWG |
| 95 mm² | 187,485 | between 3/0 and 4/0 AWG | 4/0 AWG | 3/0 AWG |
| 120 mm² | 236,823 | 237 kcmil | 250 kcmil | 4/0 AWG |
| 150 mm² | 296,029 | 296 kcmil | 300 kcmil | 250 kcmil |
| 185 mm² | 365,102 | 365 kcmil | 400 kcmil | 350 kcmil |
| 240 mm² | 473,646 | 474 kcmil | 500 kcmil | 400 kcmil |
| 300 mm² | 592,058 | 592 kcmil | 600 kcmil | 500 kcmil |
| 400 mm² | 789,410 | 789 kcmil | 800 kcmil | 750 kcmil |
| 500 mm² | 986,763 | 987 kcmil | 1000 kcmil | 900 kcmil |
| 630 mm² | 1,243,321 | 1,243 kcmil | 1250 kcmil | 1000 kcmil |
| 800 mm² | 1,578,820 | 1,579 kcmil | 1750 kcmil | 1500 kcmil |
| 1000 mm² | 1,973,525 | 1,974 kcmil | 2000 kcmil | 1750 kcmil |
kcmil to mm² chart
Above 4/0, US sizes are given in kcmil, thousands of circular mils: 250 kcmil is 250,000 cmil. The chart gives no diameter for them: cables this large are almost always stranded, and a stranded diameter depends on the stranding.
| kcmil | Area (mm²) | Metric size, same or larger | Metric size, next smaller | Ω per km |
|---|---|---|---|---|
| 250 kcmil | 127 | 150 mm² | 120 mm² | 0.169 |
| 300 kcmil | 152 | 185 mm² | 150 mm² | 0.141 |
| 350 kcmil | 177 | 185 mm² | 150 mm² | 0.121 |
| 400 kcmil | 203 | 240 mm² | 185 mm² | 0.106 |
| 500 kcmil | 253 | 300 mm² | 240 mm² | 0.0846 |
| 600 kcmil | 304 | 400 mm² | 300 mm² | 0.0705 |
| 700 kcmil | 355 | 400 mm² | 300 mm² | 0.0605 |
| 750 kcmil | 380 | 400 mm² | 300 mm² | 0.0564 |
| 800 kcmil | 405 | 500 mm² | 400 mm² | 0.0529 |
| 900 kcmil | 456 | 500 mm² | 400 mm² | 0.0470 |
| 1000 kcmil | 507 | 630 mm² | 500 mm² | 0.0423 |
| 1250 kcmil | 633 | 800 mm² | 630 mm² | 0.0339 |
| 1500 kcmil | 760 | 800 mm² | 630 mm² | 0.0282 |
| 1750 kcmil | 887 | 1000 mm² | 800 mm² | 0.0242 |
| 2000 kcmil | 1,013 | none listed | 1000 mm² | 0.0212 |
How the gauge works
AWG is defined by two sizes: 36 AWG is 0.005 in across and 4/0 (0000) is 0.46 in. The 39 steps between them grow by the same ratio, so the diameter of gauge n is:
d = 0.005 in × 92^((36 − n) ÷ 39)
- For the aught sizes, n is 0 for 1/0, −1 for 2/0, −2 for 3/0 and −3 for 4/0.
- Area in circular mils is the diameter in thousandths of an inch, squared: 12 AWG is 80.8 mils across, so 6,530 cmil. One mm² is 1,973.5 cmil.
- Every 3 gauges about doubles the area and halves the resistance. Every 6 gauges about doubles the diameter.
B&S and AWG
B&S stands for Brown & Sharpe, and the B&S gauge is another name for AWG, so the numbers match: 6 B&S is 13.3 mm². In Australia 1/0 is written 0 B&S and 2/0 is 00 B&S. Automotive cable is often sold by a nominal size, such as “6mm” or “6 B&S”, that is not its copper area. Check the real area on the cable or its datasheet, and use that area in the converter.
Solid and stranded wire
The diameters in the chart are for solid wire. A stranded conductor of the same gauge has the same copper area but measures larger, because of the gaps between the strands. To size a stranded wire, read the size printed on the insulation, or measure one strand, find its area in the converter and multiply by the number of strands.
Size, current and voltage drop
- Size is not ampacity. How much current a wire may carry depends on its insulation, how it is installed and the wiring code. The ampacity guide explains the check.
- Long runs need more. A wire big enough for the current can still drop too much voltage over a long run. Check it with the voltage drop calculator, or the 12V calculator for batteries.
- The resistance column uses the copper constant the calculator uses, on a 75 °C basis (see the method page). Cooler copper has less resistance, so a wire at room temperature measures lower.
Frequently asked questions
What is 6 B&S cable in mm²?
6 B&S is the same size as 6 AWG: 13.3 mm² of copper, 4.12 mm across as a solid wire. The nearest metric size with at least as much copper is 16 mm².
Is B&S the same as AWG?
Yes. B&S stands for Brown & Sharpe, and the B&S gauge is another name for the American Wire Gauge, so the numbers are the same. Australian automotive and solar cable is often labelled in B&S, and 0 B&S is 1/0 AWG.
What AWG is 2.5 mm²?
About 13.2 AWG, between 14 AWG (2.08 mm²) and 12 AWG (3.31 mm²). The US size with at least the same area is 12 AWG.
What AWG is 4 mm²?
About 11.2 AWG, between 12 AWG (3.31 mm²) and 10 AWG (5.26 mm²). The US size with at least the same area is 10 AWG.
What is 10 AWG in mm²?
5.26 mm², 2.59 mm across as a solid wire. The nearest metric size with at least as much copper is 6 mm².
Does a bigger gauge number mean a thicker wire?
No, the other way round. In AWG and B&S the number goes down as the wire gets thicker: 10 AWG is thicker than 14 AWG. After 1 AWG come 1/0, 2/0, 3/0 and 4/0, and larger US sizes are given in kcmil.
Does this chart give the current a wire can carry?
No. Ampacity depends on the insulation, how the cable is installed and the wiring code, so it is not a property of the size alone. Check it in the code you work under, such as the NEC, the CEC, BS 7671 or AS/NZS 3008.
Related: voltage drop calculator, 12V wire size calculator, voltage drop calculator for Canada, SWA cable size calculator (UK), ampacity vs voltage drop, how the calculator works.