Voltage Drop Calculator

Wire gauge chart and converter

Convert AWG (also sold as B&S) to mm², kcmil and diameter, and back. Every value is worked out from the AWG formula, not copied from a table.

Convert from

Size given as

1/0 is also written 0, and 2/0 as 00.

Conversion

Copper resistance at 75 °C
6 AWG13.3 mm²
B&S gauge6 B&S
Metric size, same or larger16 mm²
Metric size, next smaller10 mm²
Area13.3 mm² · 26,251 cmil
Diameter, solid4.12 mm · 0.162 in
Resistance1.61 Ω/km · 0.491 Ω/1000 ft

Choose the size with at least the same area, then check its ampacity in your code book. A size chart does not say how much current a wire may carry.

6 AWG is 13.3 mm². Metric size, same or larger: 16 mm².

Check voltage drop on 6 AWG

AWG and B&S wire gauge chart

From 4/0, the largest gauge, to 40 AWG. B&S sizes are the same: 6 B&S is 6 AWG. Values are rounded to 3 significant figures.

Solid wire. Resistance is DC, for copper at 75 °C.
AWG / B&SDiameter (in)Diameter (mm)Area (cmil)Area (mm²)Ω per 1000 ftΩ per km
4/00.46011.7211,6001070.06100.200
3/00.41010.4167,80685.00.07690.252
2/00.3659.27133,07767.40.09690.318
1/00.3258.25105,53553.50.1220.401
10.2897.3583,69342.40.1540.506
20.2586.5466,37133.60.1940.638
30.2295.8352,63526.70.2450.804
40.2045.1941,74121.20.3091.01
50.1824.6233,10216.80.3901.28
60.1624.1226,25113.30.4911.61
70.1443.6620,81810.50.6202.03
80.1283.2616,5108.370.7812.56
90.1142.9113,0936.630.9853.23
100.1022.5910,3835.261.244.08
110.09072.308,2344.171.575.14
120.08082.056,5303.311.986.48
130.07201.835,1782.622.498.17
140.06411.634,1072.083.1410.3
150.05711.453,2571.653.9613.0
160.05081.292,5831.314.9916.4
170.04531.152,0481.046.3020.7
180.04031.021,6240.8237.9426.1
190.03590.9121,2880.65310.032.9
200.03200.8121,0220.51812.641.4
210.02850.7238100.41015.952.2
220.02530.6446420.32620.165.9
230.02260.5735090.25825.383.1
240.02010.5114040.20531.9105
250.01790.4553200.16240.3132
260.01590.4052540.12950.8167
270.01420.3612020.10264.0210
280.01260.3211600.081080.7265
290.01130.2861270.0642102334
300.01000.2551010.0509128421
310.008930.22779.70.0404162531
320.007950.20263.20.0320204670
330.007080.18050.10.0254257844
340.006300.16039.80.02013251,065
350.005610.14331.50.01604091,343
360.005000.12725.00.01275161,693
370.004450.11319.80.01006512,135
380.003970.10115.70.007978202,692
390.003530.089712.50.006321,0353,394
400.003140.07999.890.005011,3054,280

mm² to AWG chart

Metric cable is sold in the IEC 60228 sizes. The equivalent gauge is the exact match. To swap a metric cable for a US one, choose the size with at least the same area.

US sizes here are the ones commonly sold: even gauges to 4 AWG, then 3, 2, 1, 1/0 to 4/0 and kcmil. Odd gauges such as 13 AWG exist but are rarely sold.
Metric sizeArea (cmil)Equivalent gaugeUS size, same or largerUS size, next smaller
0.5 mm²98720.1 AWG20 AWG22 AWG
0.75 mm²1,48018.4 AWG18 AWG20 AWG
1 mm²1,97417.2 AWG16 AWG18 AWG
1.5 mm²2,96015.4 AWG14 AWG16 AWG
2.5 mm²4,93413.2 AWG12 AWG14 AWG
4 mm²7,89411.2 AWG10 AWG12 AWG
6 mm²11,8419.4 AWG8 AWG10 AWG
10 mm²19,7357.2 AWG6 AWG8 AWG
16 mm²31,5765.2 AWG4 AWG6 AWG
25 mm²49,3383.3 AWG3 AWG4 AWG
35 mm²69,0731.8 AWG1 AWG2 AWG
50 mm²98,676between 1 and 1/0 AWG1/0 AWG1 AWG
70 mm²138,147between 2/0 and 3/0 AWG3/0 AWG2/0 AWG
95 mm²187,485between 3/0 and 4/0 AWG4/0 AWG3/0 AWG
120 mm²236,823237 kcmil250 kcmil4/0 AWG
150 mm²296,029296 kcmil300 kcmil250 kcmil
185 mm²365,102365 kcmil400 kcmil350 kcmil
240 mm²473,646474 kcmil500 kcmil400 kcmil
300 mm²592,058592 kcmil600 kcmil500 kcmil
400 mm²789,410789 kcmil800 kcmil750 kcmil
500 mm²986,763987 kcmil1000 kcmil900 kcmil
630 mm²1,243,3211,243 kcmil1250 kcmil1000 kcmil
800 mm²1,578,8201,579 kcmil1750 kcmil1500 kcmil
1000 mm²1,973,5251,974 kcmil2000 kcmil1750 kcmil

kcmil to mm² chart

Above 4/0, US sizes are given in kcmil, thousands of circular mils: 250 kcmil is 250,000 cmil. The chart gives no diameter for them: cables this large are almost always stranded, and a stranded diameter depends on the stranding.

kcmilArea (mm²)Metric size, same or largerMetric size, next smallerΩ per km
250 kcmil127150 mm²120 mm²0.169
300 kcmil152185 mm²150 mm²0.141
350 kcmil177185 mm²150 mm²0.121
400 kcmil203240 mm²185 mm²0.106
500 kcmil253300 mm²240 mm²0.0846
600 kcmil304400 mm²300 mm²0.0705
700 kcmil355400 mm²300 mm²0.0605
750 kcmil380400 mm²300 mm²0.0564
800 kcmil405500 mm²400 mm²0.0529
900 kcmil456500 mm²400 mm²0.0470
1000 kcmil507630 mm²500 mm²0.0423
1250 kcmil633800 mm²630 mm²0.0339
1500 kcmil760800 mm²630 mm²0.0282
1750 kcmil8871000 mm²800 mm²0.0242
2000 kcmil1,013none listed1000 mm²0.0212

How the gauge works

AWG is defined by two sizes: 36 AWG is 0.005 in across and 4/0 (0000) is 0.46 in. The 39 steps between them grow by the same ratio, so the diameter of gauge n is:

d = 0.005 in × 92^((36 − n) ÷ 39)

B&S and AWG

B&S stands for Brown & Sharpe, and the B&S gauge is another name for AWG, so the numbers match: 6 B&S is 13.3 mm². In Australia 1/0 is written 0 B&S and 2/0 is 00 B&S. Automotive cable is often sold by a nominal size, such as “6mm” or “6 B&S”, that is not its copper area. Check the real area on the cable or its datasheet, and use that area in the converter.

Solid and stranded wire

The diameters in the chart are for solid wire. A stranded conductor of the same gauge has the same copper area but measures larger, because of the gaps between the strands. To size a stranded wire, read the size printed on the insulation, or measure one strand, find its area in the converter and multiply by the number of strands.

Size, current and voltage drop

Frequently asked questions

What is 6 B&S cable in mm²?

6 B&S is the same size as 6 AWG: 13.3 mm² of copper, 4.12 mm across as a solid wire. The nearest metric size with at least as much copper is 16 mm².

Is B&S the same as AWG?

Yes. B&S stands for Brown & Sharpe, and the B&S gauge is another name for the American Wire Gauge, so the numbers are the same. Australian automotive and solar cable is often labelled in B&S, and 0 B&S is 1/0 AWG.

What AWG is 2.5 mm²?

About 13.2 AWG, between 14 AWG (2.08 mm²) and 12 AWG (3.31 mm²). The US size with at least the same area is 12 AWG.

What AWG is 4 mm²?

About 11.2 AWG, between 12 AWG (3.31 mm²) and 10 AWG (5.26 mm²). The US size with at least the same area is 10 AWG.

What is 10 AWG in mm²?

5.26 mm², 2.59 mm across as a solid wire. The nearest metric size with at least as much copper is 6 mm².

Does a bigger gauge number mean a thicker wire?

No, the other way round. In AWG and B&S the number goes down as the wire gets thicker: 10 AWG is thicker than 14 AWG. After 1 AWG come 1/0, 2/0, 3/0 and 4/0, and larger US sizes are given in kcmil.

Does this chart give the current a wire can carry?

No. Ampacity depends on the insulation, how the cable is installed and the wiring code, so it is not a property of the size alone. Check it in the code you work under, such as the NEC, the CEC, BS 7671 or AS/NZS 3008.

Related: voltage drop calculator, 12V wire size calculator, voltage drop calculator for Canada, SWA cable size calculator (UK), ampacity vs voltage drop, how the calculator works.