Voltage Drop Calculator

Voltage drop chart

How far you can run each wire size before the drop passes 3% (or 5%), in AWG and feet or mm² and metres. Every number comes from the same formula as the calculator.

Sizes and lengths
Supply voltage
Allowed drop
Conductor material

Longest one-way run in feet for a 3% drop: copper, 120 V, single-phase or DC.

Wire size5 A10 A15 A20 A30 A40 A50 A
14 AWG115573829191411
12 AWG182916146302318
10 AWG2901459772483629
8 AWG461230154115775846
6 AWG7333662441831229273
4 AWG1,165582388291194146116
3 AWG1,469734490367245184147
2 AWG1,852926617463309232185
1 AWG2,3361,168779584389292234
1/0 AWG2,9451,473982736491368295
2/0 AWG3,7141,8571,238928619464371
3/0 AWG4,6832,3411,5611,171780585468
4/0 AWG5,9052,9531,9681,476984738591

Voltage drop only: a small wire may not be allowed to carry the larger currents at all, so check its ampacity too (see the ampacity guide). On a balanced three-phase circuit, multiply by 1.155 (2 ÷ √3) at the same line-to-line voltage.

How far can you run 12 gauge wire?

On a 20 A circuit at 120 V, carrying the full 20 A, 12 AWG copper reaches a 3% drop at about 46 ft one way. A lighter load goes further: at 15 A it is about 61 ft. The usual US branch circuits at 3%:

CircuitAt 120 VAt 240 V
14 AWG, 15 A38 ft76 ft
12 AWG, 20 A46 ft91 ft
10 AWG, 30 A48 ft97 ft

The NEC small-conductor rule (240.4(D)) normally limits the breaker for copper 14, 12 and 10 AWG to 15, 20 and 30 A, which is why these three pairs are the usual ones. For a longer run, go up a size and check it in the calculator.

Voltage drop per 100 feet

Multiply the figure by the current and by the one-way length in hundreds of feet. The return wire is already counted. Example: 12 AWG copper, 20 A, 100 ft one way: 0.395 × 20 × 1 = 7.90 V.

Volts per amp per 100 ft of one-way run, 75 °C basis, to 3 significant figures.
Wire sizeCopperAluminum
14 AWG0.6281.03
12 AWG0.3950.649
10 AWG0.2480.408
8 AWG0.1560.257
6 AWG0.09830.162
4 AWG0.06180.102
3 AWG0.04900.0806
2 AWG0.03890.0639
1 AWG0.03080.0507
1/0 AWG0.02440.0402
2/0 AWG0.01940.0319
3/0 AWG0.01540.0253
4/0 AWG0.01220.0200
250 kcmil0.01030.0170
300 kcmil0.008600.0141
350 kcmil0.007370.0121
400 kcmil0.006450.0106
500 kcmil0.005160.00848

The 3% rule

The 3% figure is for one branch circuit or feeder; 5% is the total from where the supply comes in to the load. What it means depends on where you are:

How the chart is worked out

L = (target ÷ 100 × V × CM) ÷ (2 × K × I)

This is the voltage drop formula solved for the one-way length L, in feet. K is 12.9 for copper and 21.2 for aluminum on a 75 °C basis; in metric, ρ is 0.02145 and 0.03524 ohm·mm² per metre with the area in mm². The chart is for DC and single-phase circuits. Reactance, which matters for large conductors on AC, is left out. Details are on the method page.

Frequently asked questions

What is the 3% voltage drop rule?

Keep the drop in any one branch circuit or feeder to 3% of the supply voltage, and the total from the service to the load to 5%. In the US these figures are informational notes in the NEC, not requirements unless your authority adopts them. In Canada, Rule 8-102 of the CEC makes them a rule. In the UK, BS 7671 treats 3% for lighting and 5% for other uses as deemed to satisfy.

How far can you run 12 gauge wire on a 20 amp circuit?

About 46 ft one way at 120 V, carrying the full 20 A, before the drop passes 3%; about 91 ft at 240 V. At 15 A it is about 61 ft at 120 V. Past that, use 10 AWG or check the run in the calculator.

How far can you run 14 gauge wire?

On a 15 A circuit at 120 V, about 38 ft one way at full load before the drop passes 3%, or 76 ft at 240 V.

How far can you run 10 gauge wire at 30 amps?

About 48 ft one way at 120 V and 97 ft at 240 V, at a 3% drop.

What is the voltage drop per 100 feet of 12 gauge wire?

About 0.395 V per amp for 100 ft one way in copper, counting the return wire. At 20 A that is 7.9 V, or 6.6% of 120 V.

Does a 5% drop let me run further?

Yes, 5/3 as far: 5% is two-thirds more than 3%. But in the US and Canada 5% is the total for feeder and branch circuit together, so a branch circuit on its own usually gets 3% or less.

Related: voltage drop calculator, wire gauge chart (AWG to mm²), how to calculate voltage drop, ampacity vs voltage drop, how the calculator works.