Voltage Drop Calculator

Well pump wire size calculator

Wire size for a submersible well pump. Enter the cable run from the panel to the motor, with the pump depth included, and the motor’s maximum nameplate amps.

What do you want to know?

Smallest wire for 5%

Copper
230 V222.69 VSOURCELOAD10 AWG copper490 ft
Wire size10 AWG
Metric, same or larger6 mm²
Area5.26 mm²
Voltage drop7.31 V
Percent drop3.18 %
At the load222.69 V

Within 5% target

At other limits

  1. 8 AWG at 3%
  2. 10 AWG at 5%
  3. 14 AWG at 10%

Worked out with

  • Copper at 75 °C (K = 12.9)
  • 490 ft one way; the return wire is added
  • 6 A, the current the load draws
  • Single-phase, 230 V
Why other calculators give a different size

10 AWG. Drop 7.31 volts, 3.18 percent. Within 5% target.

Report a problem with this result

How this is worked out

V = 2 × K × I × L ÷ CM

2 × 12.9 × 6 A × 490 ft ÷ 10,383 CM = 7.31 V

7.31 V ÷ 230 V × 100 = 3.18 %. At the load: 230 V − 7.31 V = 222.69 V.

  • L is the one-way length; the 2 counts the return conductor.
  • K is 12.9 for copper and 21.2 for aluminum, in ohm·CM per foot on a 75 °C basis.
  • Not checked here: temperature derating, conduit fill, power factor and code compliance.

Method and sources

Inputs

Wire sizes
Length in
Circuit type
Supply voltage

What the load actually draws, not the breaker size.

Source to load. Don't double it: the return wire is counted for you.

Conductor material
Allowed drop

Pump makers size cable for a 5% drop at the motor’s maximum nameplate amps.

After derating for temperature and conduit fill. The tool does not hold ampacity tables.

Measure to the motor, not the well head

Which current and which drop

Worked example: a 1/2 hp pump, 490 ft of cable

A 1/2 hp 2-wire pump draws about 6 A at 230 V and 12 A at 115 V at maximum load (Franklin Electric’s figures for its motors). Over 490 ft of copper cable:

SupplyAt 5%At 3%
230 V, 6 A10 AWG
3.18 %
8 AWG
2.00 %
115 V, 12 A4 AWG
3.16 %
3 AWG
2.51 %

At 230 V, 12 AWG would come to 5.05 %, just over 5%, so the answer is 10 AWG. The same pump at 115 V draws twice the current and needs 4 AWG: one reason pumps above 1/2 hp are 230 V. The calculator above starts with the 230 V case.

This calculator and the pump maker’s table

This calculator uses copper resistance at 75 °C (K = 12.9; see the method page), a warm-wire figure. In spot checks its allowed lengths come out roughly 5–30% shorter than pump makers’ tables, so treat its answer as a cautious estimate. Where the motor maker’s chart and this page differ, follow the maker’s chart and the electrical code; CentriPro notes that the NEC takes precedence over any maker’s chart.

Cable, splices and grounding

Frequently asked questions

Do I include the well depth in the wire length?

Yes. Pump makers measure the cable from the service entrance to the motor, so the length is the run to the well plus the depth the pump is set at. A 150 ft trench to a pump set at 340 ft is 490 ft of cable. Enter that one way: the calculator counts the return wire.

Which amps do I use for a well pump?

The motor’s maximum nameplate amps, also called service factor amps, from the motor label or the maker’s data. Pump makers size cable at that current, not at full-load amps, and amps differ between brands, so use the figure for your motor.

What voltage drop do pump makers allow?

Franklin Electric, Grundfos and CentriPro size their cable tables for a 5% drop at maximum nameplate amps: the motor gets at least 95% of the voltage at the service entrance. Franklin gives a 3% option too. Supply voltage at the motor should stay within 10% of its rating.

Does the control box change the length?

No. A single-phase control box without a line contactor can sit anywhere along the run; you still measure the whole cable to the motor. With a line contactor, Franklin and Grundfos limit the cable before the box to a quarter of the allowed length.

Why is a 115 V pump so much harder to wire?

The same horsepower draws about twice the current at 115 V as at 230 V, so the drop doubles on the same wire. Franklin makes 115 V submersible motors only up to 1/2 hp; larger single-phase pumps are 230 V.

Can I use two wire sizes on one run?

Yes. Pump makers add up the share of the allowed length each section uses, and the total must stay at or under 100%. An existing buried run uses part of the budget, so the cable down the well must fit what is left. To check a run like that here, work out each section with “Is my wire OK?” and add the two percentages.