Voltage drop calculator
Wire size and voltage drop for DC, single-phase and three-phase circuits. The answer updates as you type, with the working shown. On a 12 V or 24 V battery system? Use the 12V wire size calculator.
Smallest wire for 3%
Copper| Wire size | 12 AWG |
| Metric, same or larger | 4 mm² |
| Area | 3.31 mm² |
| Voltage drop | 2.96 V |
| Percent drop | 2.47 % |
| At the load | 117.04 V |
Within 3% target
At other limits
- 12 AWG at 3%
- 14 AWG at 5%
- 14 AWG at 10%
Worked out with
- Copper at 75 °C (K = 12.9)
- 50 ft one way; the return wire is added
- 15 A, the current the load draws
- Single-phase, 120 V
12 AWG. Drop 2.96 volts, 2.47 percent. Within 3% target.
Result from https://voltagedropcalculator.app/voltage-drop-calculator?phase=single&voltage=120¤t=15&length=50&material=copper&target=3&mode=find. This checks voltage drop only, not code compliance.
How this is worked out
V = 2 × K × I × L ÷ CM
2 × 12.9 × 15 A × 50 ft ÷ 6,530 CM = 2.96 V
2.96 V ÷ 120 V × 100 = 2.47 %. At the load: 120 V − 2.96 V = 117.04 V.
- L is the one-way length; the 2 counts the return conductor.
- K is 12.9 for copper and 21.2 for aluminum, in ohm·CM per foot on a 75 °C basis.
- Not checked here: temperature derating, conduit fill, power factor and code compliance.
How the number is made
For DC and single-phase circuits the drop is V = 2 × K × I × L ÷ CM. I is the load current in amps, L is the one-way length in feet, CM is the conductor area in circular mils, and K is 12.9 for copper or 21.2 for aluminum. The 2 counts the return conductor. For a balanced three-phase circuit the 2 becomes √3 and the voltage is line to line (see the three-phase example). Details and sources are on the method page.
Voltage drop and ampacity are two different checks
The drop check protects the equipment at the far end: the motor starts, the lights stay bright, the fridge runs. The ampacity check protects the wire against heating. Either one can set the wire size. The ampacity guide explains which one governs.
Frequently asked questions
What is voltage drop?
Voltage drop is the voltage lost along the wire because of its resistance. A longer run or a smaller wire loses more voltage before the load.
Is 3% a legal limit?
In the US, no. The 3% branch and 5% total figures are informational guidance in the National Electrical Code (NEC §210.19 informational note), and a local authority may adopt them as requirements, so check yours. In Canada, yes: the Canadian Electrical Code, Rule 8-102, makes 3% per feeder or branch circuit and 5% in total a rule. See the Canadian calculator. In the UK, BS 7671 treats 3% for lighting and 5% for other uses, from the origin of the installation, as deemed to satisfy, not as a hard limit. See the SWA cable calculator. The voltage drop chart sets out the rule by country.
Does the length include the return wire?
Enter the one-way distance from the source to the load. The formula counts the return conductor (the 2 in V = 2 × K × I × L ÷ CM).
Why does another calculator give a different answer?
Usually because of a setting you can't see: a different target (3% or 5%), a different wire temperature, a power factor on AC, a "residential" or "commercial" mode, or a length entered one way where another tool wants the round trip. This page lists every setting it used under the answer ("Worked out with"), so you can match another tool or a forum reply. The method page explains each one.
Do I use the breaker size or the load?
The load: the current it actually draws while running, from its label or manual. Voltage drop grows with the current, so sizing on the breaker rating gives a bigger wire than the run needs. If you only know watts, choose W next to the load and the calculator divides by the voltage.
Does a bigger wire mean a bigger breaker?
No. The breaker protects the circuit and stays the size the load and circuit need. Voltage drop only changes the wire. A larger wire can be harder to connect: check the largest size the breaker and device terminals take.
Copper or aluminum: what changes?
Aluminum has a constant of 21.2 against 12.9 for copper, so the same drop needs about 1.6 times the conductor area. Switch the conductor material and the answer updates.
Can I use mm² and metres?
Yes. Choose mm² and metres under Inputs. The sizes are the standard metric series from 0.75 to 300 mm², on the same 75 °C basis as the AWG sizes, and the calculator remembers your choice. In the UK, Ireland, Australia and New Zealand it starts in mm² and metres. To convert a size between AWG and mm², use the wire gauge chart.
Does it do three-phase?
Yes. Choose Three-phase under Circuit type, then the line-to-line voltage (208, 400, 480 or 600 V, or another under Other) and the current in each line. The formula uses √3 in place of 2 and assumes a balanced load.
Does this check ampacity?
It checks ampacity only against a value you enter from your code book, after derating. The tool does not hold ampacity tables.
When should I call an electrician?
This tool checks voltage drop only, not code compliance. New circuits, sub-panels and power to an outbuilding often need a permit, and in some places only a licensed electrician may do the work. Check with your local authority. The result lists every input, so you can take it to an electrician and ask the right questions.
Learn more: 12V wire size calculator, boat wire size calculator (ABYC), solar wire size calculator, well pump wire size calculator, voltage drop chart (how far each size can run), SWA cable size calculator (UK, BS 7671), wire gauge chart (AWG to mm²), voltage drop calculator for Canada (CEC), how to calculate voltage drop, ampacity vs voltage drop, how this calculator works.